APPX
Appendix 1 Error Codes
729
A
2320H Remote
password
setting error
The start I/O number of the
remote password target module is
set to other than 0H to 0FF0H.
There is a problem on the slot
specified by the start I/O number
of the remote password setting.
(1) No module is mounted.
(2) The mounted intelligent function
module does not support the
remote password setting.
Stop Set the start I/O number of the remote
password target module within the
range 0H to 0FF0H.
On the specified slot, mount an
intelligent function module that
supports the remote password setting.
System
configuration
information
At power-on,
at RESET, at
STOP RUN
state
2321H Remote
password
setting error
In a multiple CPU system, the
module controlled by another CPU
module is specified by the start I/O
number of the remote password
setting.
Stop Check and correct the remote
password setting.
System
configuration
information
At power-on,
at RESET, at
STOP RUN
state
2400H Module
verification error
The module information at power-
on differs from the information of
modules actually mounted.
The I/O module or intelligent
function module is not mounted
properly or was removed during
operation.
Stop/
continue
Check the detailed information (system
configuration information) of the error
by executing module diagnostics using
the engineering tool and check the
module corresponding to the displayed
slot number.
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the error module.
Please consult your local Mitsubishi
representative.
System
configuration
information
Always
2401H Module
verification error
A CPU module, I/O module, or
intelligent function module was
mounted on the base unit during
operation.
Stop/
continue
Check the detailed information (system
configuration information) of the error
by executing module diagnostics using
the engineering tool and check the
module corresponding to the displayed
slot number.
Do not mount a CPU module, I/O
module, nor intelligent function module
during operation.
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the error module.
Please consult your local Mitsubishi
representative.
System
configuration
information
Always
2420H Fuse blown
error
The output module with a blown
fuse has been detected.
Stop/
continue
Check the FUSE LED of each output
module, and replace the one with the
FUSE LED on.
Check the detailed information (system
configuration information) of the error
b
y executing module diagnostics using
the engineering tool, and replace the
module corresponding to the displayed
slot number.
System
configuration
information
Always
2440H Module major
error
In a multiple CPU system, the
control CPU setting in the system
parameters is different from that of
other CPU modules.
In a multiple CPU system, other
CPU modules (SIL2 Process CPU
or Safety CPU) have detected a
parameter verification error.
An error has been detected in the
I/O module or intelligent function
module during the initial
processing.
Stop Correct the system parameter settings
for the CPU No.2 and later in
accordance with those of the CPU
No.1.
Eliminate the error cause of another
CPU module (Safety CPU or SIL2
Process CPU).
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the error module.
Please consult your local Mitsubishi
representative.
System
configuration
information
At power-on,
at RESET
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing