Appendix 1 Error Codes
24C3H System bus
error
An error was detected on the
system bus.
Stop CPU module
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
base unit, extension cable, or module
(I/O module or intelligent function
module) connected. Please consult
your local Mitsubishi representative.
Redundant function module
The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
System
configuration
information
At module
access
24C4H System bus
error
An error was detected on the
system bus.
Stop Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the base unit,
extension cable, or module (I/O module
or intelligent function module)
connected. Please consult your local
Mitsubishi representative.
System
configuration
information
At module
access
24C5H
24C6H System bus
error
An error was detected on the
system bus.
Stop CPU module
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or extension cable. Please consult your
local Mitsubishi representative.
Redundant function module
The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
At module
access
24C8H System bus
error
An error was detected on the
system bus.
Stop Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the extension
cable, or module (I/O module or
intelligent function module) connected.
Please consult your local Mitsubishi
representative.
At power-on,
at RESET
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents