Appendix 1 Error Codes
731
A
24C0H System bus
error
An error was detected on the
system bus.
Stop CPU module
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
base unit, extension cable, or module
(I/O module or intelligent function
module) connected. Please consult
your local Mitsubishi representative.
Redundant function module
The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
System
configuration
information
At module
access
24C1H
24C2H System bus
error
The I/O module or intelligent
function module is not mounted
properly or was removed during
operation.
An error was detected on the
system bus.
Stop CPU module
Check the detailed information (system
configuration information) of the error
by executing module diagnostics using
the engineering tool and check the
module corresponding to the displayed
slot number.
Check the connection status of the
extension cable.
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
base unit, extension cable, or module
(I/O module or intelligent function
module) connected. Please consult
your local Mitsubishi representative.
Redundant function module
The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
System
configuration
information
Always
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents