APPX
Appendix 1 Error Codes
787
A
Codes of errors detected by other than the self-diagnostic function (6F00H to 6FFFH)
The following table lists the codes of errors, other than those detected by the self-diagnostic function of the CPU module.
Error
code
Error name Error details and cause Action
6F00H Transient
execution error
The internal buffer area for transient processing is used to
the maximum.
Temporarily stop transient transmissions, or reduce the
frequency. Then, perform transmissions again. Or, add the
COM instruction to the programmable controller CPU and
increase the frequency. If the same error occurs again, the
possible cause is a hardware failure of the redundant
function module. Please consult your local Mitsubishi
representative.
6F01H Transient
transmission
timeout error
In transient transmission, timeout has occurred without
transmission completion.
Review the network status. If the same error occurs again,
the possible cause is a hardware failure of the redundant
function module. Please consult your local Mitsubishi
representative.
6F02H Module error An error has been detected in the redundant function
module.
Please consult your local Mitsubishi representative.
6F23H
6F24H
6F25H Module
communication
test error
The operating status of the CPU module is in a state other
than STOP. (A test cannot be executed.)
Change the operating status of the CPU module to STOP,
and execute a module communication test.
6F27H Module
communication
test being
executed
A module communication test execution request was
received during the test.
A module communication test termination request was
received during the test.
Since the module communication test is being executed,
execute the request again after the completion of the test.
6F28H Module being
changed online
A module communication test execution request was
received during online module change.
A module communication test termination request was
received during online module change.
Since a module is being changed online, execute the
request again after the completion of the change.
6F29H Module
communication
test error
A module communication test execution request was
received in the state where tracking cables are connected
incorrectly.
Connect one end of a tracking cable to the IN connector and
the other end to the OUT connector of the test target
redundant function module, and execute the request again.
6F30H Transient
execution error
(redundant
function module
communication
being stopped)
Data communications cannot be performed with the other
system because of any of the following reasons:
The CPU module of the other system is powered off or in a
reset state.
The tracking communication stops due to an error in the
CPU module of the own or other system.
Tracking cables are disconnected or incorrectly connected,
or failed.
The redundant function module of the own or other system is
being changed online, a module communication test is being
performed for the module, or a hardware failure has
occurred in the module.
If a WDT error has occurred in the CPU module of the own
or other system, eliminate the error cause and then execute
the operation again.
Check that there is no error or failure in the CPU module,
tracking cables, redundant function modules, and perform a
retry. Or, perform a retry after the online module change
processing or the module communication test ends. If the
same error code is displayed again, the possible cause is a
hardware failure of the CPU module, redundant function
module, base unit, or tracking cable. Please consult your
local Mitsubishi representative.
6F40H Transient
execution error
The number of transient transmission requests exceeded the
upper limit of simultaneously processable requests.
Temporarily stop transient transmissions, or reduce the
frequency. Then, perform transmissions again.
6F44H Transient frame
error
An invalid transient frame was received. Check and correct the request data (send data) on the
request source side, and perform transmissions again.
6F4AH
6F4BH
6F4CH
6F4DH
6F4EH
6F60H Module error An error has been detected in the redundant function
module.
Please consult your local Mitsubishi representative.