792
APPX
Appendix 2 Event List
00A00 System Warning Error detection in
the other system
An error was detected in the other
system.
Error
description (the
other system)
00C02 Abnormal response
from/to the other
system
• An abnormal response was sent to the
other system.
• An abnormal response was sent from
the other system.
Target station
information
00C27 Tracking
communication stop
Tracking communication has stopped as
a result of any of the following:
• The standby system CPU module has
been powered off or reset.
• Hardware failure of the CPU module
has occurred.
• An error has occurred in the redundant
function module.
• A WDT error has occurred.
• Tracking cables has been pulled out or
disconnected.
Cause of
tracking
communication
stop
00C28 Retry • A tracking communication retry was
performed due to the change in
communication route caused by
loopback.
• A tracking communication retry was
performed due to a line status error,
such as faulty cable and incorrect
connector connection.
00F00 System switching
(by the system)
The systems were switched due to the
cause on the redundant system side.
System
switching
information
00F01 Auto memory copy
(control system)
The control system automatically copied
its memory to the standby system.
00F02 Auto memory copy
(standby system)
The memory of the control system was
automatically copied to the standby
system.
1000
and
after
Error When a self-diagnostic error occurs, the error is stored as an event.
Event
code
Event
type
Event
category
Detected event Description Detailed information
Detailed
information 1
Detailed
information 2
Detailed