844
APPX
Appendix 5 List of Special Register Areas
SD113 to
SD143
Detailed
information 2
Detailed
information 2
■SD114: Program error code
(29) Error information of other stations (CC-Link IE Field)
■SD81: With or without specification
b0: Error classification
b1: Error code
b2: Date (yyyymmdd)
b3: Time (hhmmss)
b4: Day of the week
b5: Detailed error information 1
b6: Detailed error information 2
b7 to bF: Detailed error information 3 to detailed error information 10
■SD82: Error classification
■SD83: Error code
■SD84 to SD85: Date (yyyymmdd)
• SD84: Lower word of date (yyyymmdd)
• SD85: Upper word of date (yyyymmdd)
■SD86 to SD87: Time (hhmmss)
• SD86: Lower word of time (hhmmss)
• SD87: Upper word of time (hhmmss)
■SD88: Day of the week
■SD89: Detailed error information 1
■SD90: Detailed error information 2
■SD91 to SD98: Detailed error information 3 to 10
S (Error) ALL
SD150 Power-off/power
supply voltage
drop detection
status
Power-off/power
supply voltage
drop detection
status (bit
pattern)
0: Power-on/
normal
voltage
1: Power-off/
voltage drop
detected/no
power supply
module
• For the redundant power supply base unit, power supply module status
(power is shut off, power supply voltage drop (not including a momentary
power failure) is detected, or an empty slot for the power-supply module
exists) is stored using the following bit pattern.
• In a multiple CPU system, the status is stored only to the CPU module
No.1.
(1) Powered-off/power supply voltage dropped (power supply module 1)
b0:Main base unit
b1 to b7: 1st to 7th level of the extension base unit
(2) Powered-off/power supply voltage dropped (power supply module 2)
b8: Main base unit
b9 to b15: 1st to 7th level of the extension base unit
S (Status
change)
Rn
*1
RnP
RnPSF
SD151 Power supply
failure detection
status
Power supply
failure detection
status (bit
pattern)
0: Not detected/
power-off/no
power supply
module
1: Detected
• For the redundant power supply base unit, failure detection status of the
power supply module is stored using the following bit pattern.
• Bits corresponding to power-off or empty slots for the power supply
module turn off.
• In a multiple CPU system, the status is stored only to the CPU module
No.1.
(1) Failure detection status of the power supply module 1
b0:Main base unit
b1 to b7: 1st to 7th level of the extension base unit
(2) Failure detection status of the power supply module 2
b8: Main base unit
b9 to b15: 1st to 7th level of the extension base unit
S (Status
change)
Rn
*1
RnP
RnPSF
No. Name Data stored Details Set by
(setting
timing)
CPU
bF b6b7 b5 b4 b3 b2 b1 b0
b0b15
(2) (1)
b7 b1 b2 b8 b9
b0b15
(2) (1)
b7 b1 b2 b8 b9