EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R-R6SFM - Page 854

Mitsubishi Electric MELSEC iQ-R-R6SFM
1028 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
852
APPX
Appendix 5 List of Special Register Areas
*1 There are restrictions on the firmware version of the supported CPU module and software version of the engineering tool. ( Page
1008 Added and Enhanced Functions)
SD530 Scan program
execution time
Scan program
execution time (unit:
ms)
The execution time of the scan program for one scan is stored
into SD530 and SD531 (it is measured in increments of s).
SD530: stores a value in the ms place (storage range: 0 to 65535)
SD531: stores a value in the s place (storage range: 0 to 999)
These areas are cleared to 0 when the operating status of the
CPU module is switched from STOP to RUN.
In a redundant system, when the operating status of the CPU
module is RUN state, these areas are cleared to 0 at the system
switching.
S (Every END) ALL
SD531 Scan program
execution time (unit:
s)
ALL
No. Name Data stored Details Set by
(setting
timing)
CPU

Table of Contents

Related product manuals