100
Item
Description Setting range
Condition specification Select this when data are to be sampled based on the device or step No. specification. -
Device
specification
Select this when device data is specified. -
Device Any of the devices listed in Section 6.2 (3) can be set. -
Conditional
formula
For word device
"=": Data are sampled when the current value of the specified device is equal to the
condition value.
"During change": Data are sampled when the current value of the specified device
is changed.
For bit device
"PLS": Data are sampled when the status of the specified device is changed from
off to on.
"PLF": Data are sampled when the status of the specified device is changed from
on to off.
For word device
"=", "During change"
For bit device
"PLS", "PLF"
Radix Set a radix of the condition value for the word device. DEC or HEX
Value Set a value that is compared with a device value.
Decimal: -32768 to 32767
Hexadecimal: 0
H
to FFFF
H
Step No.
specification
Select this so that data will be sampled when a condition is met in the specified step. -
Program name
Enter a name of the program in which data are sampled when the condition is met in
the specified step.
Eight alphanumeric characters or
less
Step No. Set a step number of the step where data are to be sampled when the condition is met. 0 to 266240
Execution
condition
Select a data sampling condition from the following.
"Always": Data are always sampled in the specified step.
"ON": Data are sampled when the result of the operation in the specified step is true.
"OFF": Data are sampled when the result of the operation in the specified step is
false.
"PLS": Data are sampled at the time the result of the operation in the specified step is
changed from false to true.
"PLF": Data are sampled at the time the result of the operation in the specified step is
changed from true to false.
"Always",
"ON",
"OFF",
"PLS",
"PLF"