6.1 Target Data
The target data is device memory data in the CPU module, which is saved on an SD memory card with time stamp.
(1) Data type
The following data types can be specified for data logging of the device memory.
*1 The specified size ranges from 1 to 256.
The number of points is calculated for each setting No. and the total number of points is used.
In the following case, the total number of points is eight.
Setting No.1 Data type (String), specified size (1) 1 point
Setting No.2 Data type (String), specified size (5) 3 points
Setting No.3 Data type (Double precision real number) 4 points
(2) Devices available for sampling
The following lists the devices whose data can be specified as sampling data.
*1 The built-in I/O function does not support the U\G specification.
*2 Digit specification of bit device is available only for K1 to K8.
*3 T (contact), ST (contact), and C (contact) are specified with TS, SS, and CS respectively.
*4 T (coil), ST (coil), and C (coil) are specified with TC, SC, and CC respectively.
For the above devices (except for FX, FY, FD, BL\S, and bit specification of word device), index modification
can be specified although indirect specification is not allowed.
Data type Number of device points Data type Number of device points
Bit 1
Single precision real
number
2
Word (unsigned) 1
Double precision real
number
4
Double word (unsigned) 2 String
Specified size/2
*1
Word (signed) 1
Raw
Specified size/2
*1
Double word (signed) 2
Type Description
Bit device
X (DX), Y (DY), M, L, F, SM, V, B, SB, T (contact)
*3
, T (coil)
*4
, ST (contact)
*3
, ST (coil)
*4
, C (contact)
*3
, C (coil)
*4
,
FX, FY, BL\S
Bit specification of word device:
D, D (extended data register), SD, W, W (extended link register), SW, R, ZR, FD, U\G
*1
Word device
T (current value), ST (current value), C (current value), D, D (extended data register), SD, W, W (extended link
register), SW, R, Z, ZR, FD, U\G
*1
Digit specification of bit device
*2
: X, Y, M, L, F, SM, V, B, SB, BL\S
Ex.

Table of Contents