142
10.1.2 Trigger logging
The following shows values of the time required for outputting a total of 200 records before and after a trigger (100
records for each) to a file when trigger logging is performed.
(1) Measurement condition
(2) Measurement results
(Unit: ms)
Item Description
Scan time 1.0 ms
Buffer capacity 128 bytes per setting (default)
Data logging setting
Sampling Each scanning cycle
Data Data: Data register (D) (Data type: word (signed) (decimal))
CSV output The Date (default output format) and Index columns are output.
SD memory card L1MEM-2GBSD
CPU module
Device points
16 (16 points × 1
setting)
64 (64 points × 1
setting)
128 (128 points × 1
setting)
256 (128 points × 2
setting)
1280 (128 points ×
10 setting)
L02CPU 2.0 3.0 4.0 7.0 30.0
L26CPU-BT 2.0 2.5 3.0 5.5 25.0