112
8.4.12 Finish
Name the data logging and finish the setting.
(1) Setting screen
(2) Setting items
Item Description Setting range
Data logging name Specify a name for the current setting.
32 one-byte or 16 two-byte characters
or less
Total Size of Output Logging Files
The total size of the logging files output for the setting is displayed. The total
size can be adjusted with the items output to CSV files. Refer to the calculation
formulas. (
Page 33, Section 3.3.2)
-
Required capacity
The buffer capacity required for the specified number of logging records is
displayed. If the size of the current setting exceeds the buffer capacity, it is
displayed in red. (
Page 64, Section 6.5)
-
Current set capacity The buffer capacity used by the currently editing project is displayed.
Setting Buffer Capacity
The "Buffer Capacity Setting" dialog box appears. Set a buffer capacity for
settings No.1 to No.10.
32 to 4832k bytes