No. Error cause
Timing of
occurrence
Value in special register
(Data logging error cause
information)
Error response
No.
9 Data logging registration was attempted to a failed memory.
Registration
200
H
4021
H
10
In registration of the data logging, a nonexistent program name was
specified.
201
H
4022
H
11
A program name (which exists in the CPU module but is not registered to the
program setting in PLC Parameter) was specified in registration of the data
logging.
202
H
4083
H
12
In registration of the data logging, a nonexistent device number was
specified.
203
H
4031
H
13
In registration of the data logging, a nonexistent step number or any other
than the head step number of an instruction was specified.
204
H
4088
H
14
Registration of the trigger logging was attempted with the trigger condition(s)
already met.
205
H
4064
H
15
When the operation in the case of exceeding the number of saved files is set
to "Stop", the data logging registration was attempted even though the
number of existing saved files is the specified number or more. Or, when the
operation in the case of exceeding the number of saved files is set to
"Overwrite", the data logging registration was attempted even though the
number of existing saved files is more than the specified number.
Registration
207
H
4277
H
16
Writing or deleting data logging settings, or data logging operation was
attempted to a setting that has been already registered.
Writing settings
Deleting
settings
Registration
-
4060
H
17
While the data logging function is in operation (the logging status is
"Executing", "Saving the logging data", "Completed", "Pausing", or "Error"),
registration of a data logging was attempted to the same destination as the
currently executing data logging.
Registration
209
H
427B
H
18
During online change, registration of a data logging, in which "Step No." is
specified in "Sampling" or "Trigger", was attempted.
20A
H
410A
H
19
While the trigger logging function is in operation with a device specified in
Trigger (the logging status is "Executing", "Saving the logging data",
"Completed", "Pausing", or "Error"), registration of a trigger logging was
attempted with a device specified in Trigger.
20B
H
4272
H
20
Registration of a data logging was attempted during execution of the
sampling trace function.
20C
H
4273
H
21
Writing or deleting data logging settings, or data logging registration was
attempted during execution of auto logging.
Writing settings
Deleting
settings
Registration
-
4275
H
22
During execution of auto logging, a data logging was not registered due to
registration failure of another setting No.
Registration
20D
H
-
23
Registration of a data logging, in which an invalid device name was
specified, was attempted.
20E
H
4030
H
24
Registration of a data logging, in which an invalid device modification was
specified, was attempted.
20F
H
4032
H
25
Re-registration of the previously registered data logging setting was
attempted. However, the corresponding file does not exist.
211
H
41C5
H
26
Data logging registration was attempted to a memory where no common
setting exists.
212
H
427A
H
27
Registration of a trigger logging was attempted even though the specified
number of records has exceeded the number of records that can be collected
for the specified data logging buffer capacity.
215
H
4274
H