34
Output of the following information can be disabled. ( Page 107, Section 8.4.9)
Date and time column
Trigger information column (selectable only for trigger logging)
Index column
Data sampling interval column
Execution program name column
Execution step No. column
Comment line
(1) File information line
Information on the file is displayed.
*1 The size of the File information line is the total of the following. (When outputting a comment)
9 (File type) + 2 (File version) + 1 (Data type information
line number) + 1 (Line No. of Data name line number) +
1 (Data start
line number) + 1 (Comment line number) + 5 (number of commas) + 2 (CR + LF)
= 22 bytes
(2) Comment line
A comment is displayed.
*1 The size of the Comment line is the total of the following.
The size of the characters used for the comment (1 byte for each one-byte character, 2 bytes for each two-byte
character) + 2 (CR + LF)
Item Description
Size
*1
File type [LOGGING] is output. 9 bytes
File version File version (fixed to L1) 2 bytes
Data type information line
number
Line number indicating the Data type information line is entered. 1 byte
Data name line number Line number indicating the Data name line is entered. 1 byte
Data start line number Line number indicating the first of the data lines is entered. 1 byte
Comment line number
Line number indicating the Comment line is entered. If the Comment line data are not to
be output, this field is left blank.
0 to 1 byte
Item Description
Size
*1
Comment
A comment set in the configuration tool is output. (Up to 512 one-byte or 256 two-byte
characters can be output. If there is no setting, blank space is output.)
0 to 512 bytes