3
[Design Precautions]
[Design Precautions]
[Installation Precautions]
[Installation Precautions]
WARNING
For the operating status of each station after a communication failure, refer to relevant manuals for
each network. Incorrect output or malfunction due to a communication failure may result in an
accident.
When changing data from a peripheral device connected to the CPU module during operation,
configure an interlock circuit in the program to ensure that the entire system will always operate
safely. For other controls to a running programmable controller (such as program modification or
operating status change), read relevant manuals carefully and ensure the safety before the
operation. Especially, in the case of a control from an external device to a remote programmable
controller, immediate action cannot be taken for a problem on the programmable controller due to a
communication failure. To prevent this, configure an interlock circuit in the program, and determine
corrective actions to be taken between the external device and CPU module in case of a
communication failure.
An absolute position restoration by the positioning function may turn off the servo-on signal (servo
off) for approximately 20ms, and the motor may run unexpectedly. If this causes a problem, provide
an electromagnetic brake to lock the motor during absolute position restoration.
CAUTION
Do not install the control lines or communication cables together with the main circuit lines or power
cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction
due to noise.
During control of an inductive load such as a lamp, heater, or solenoid valve, a large current
(approximately ten times greater than normal) may flow when the output is turned from off to on.
Therefore, use a module that has a sufficient current rating.
WARNING
Shut off the external power supply for the system in all phases before mounting or removing a
module. Failure to do so may result in electric shock or cause the module to fail or malfunction.
CAUTION
Use the programmable controller in an environment that meets the general specifications in the
MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection). Failure to
do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
To interconnect modules, engage the respective connectors and securely lock the module joint
levers. Incorrect interconnection may cause malfunction, failure, or drop of the module.
Do not directly touch any conductive parts and electronic components of the module. Doing so can
cause malfunction or failure of the module.