CHAPTER 6 DATA LOGGING FUNCTION
6
6.8 Precautions for the data logging function
(12)Changing clock data
Do not change clock data of the CPU module during execution of data logging. Doing so will cause incorrect
"Date" column information to be output to the CSV file. (Even if clock data are changed, data are collected at the
specified intervals or timing. Therefore, changed clock data will be output in the Date column of the CSV file.)
(13)Sampling timing when the display unit is attached
An error of up to ±100µs may occur in the sampling timing when the display unit is attached.
A time value is set for "Time specification" of "Sampling", without setting of data sampling at the
END processing.
Ex.