4 - 10
4 PARAMETERS FOR POSITIONING CONTROL
4.2.4 Command in-position range
The command in-position is the difference between the positioning address (command
position) and feed current value.
Once the value for the command in-position has been set, the command in-position
signal (M2403+20n) turns on when the difference between the command position and
the feed current value enters the set range [(command position - feed current value) ï‚£
(command in-position range)].
The command in-position range check is executed continuously during position control.
Command in-position
( M2403+20n )
Position
control
start
Command in-position
setting value
Speed-position
switching control
start
Speed/position switching
Command in-position
setting value
ON
OFF
Execution of command in-position check Execution of command
in-position check
V
t
(1) Command in-position can be set within the following range.
(a) Q173DSCPU/Q172DSCPU use
1 ï‚£ Command in-position range ï‚£ 2147483647
(b) Q173DCPU(-S1)/Q172DCPU(-S1) use
1 ï‚£ Command in-position range ï‚´
Number of pulses per rotation (AP)
Travel value per rotation (AL)
ï‚£ 32767