159
CHAPTER 9 PROGRAMMING
9
9.3 Program Example
(4) Devices used by user
Device Description
X20 Main A/D converter module Digital operation value read command
QX10 (X20 to X2F)
X22 Error reset command
X24 Main A/D converter module Maximum value/minimum value read command
X26 Main A/D converter module Maximum value/minimum value reset command
X28
Extension A/D converter module Maximum value/minimum value read
command
X2A
Extension A/D converter module Maximum value/minimum value reset
command
X1007 Warning flag
NZ2GF2BN-60AD4 (RX0 to RX1F)
X1009 Initial data setting completed flag
X100A Error flag
X100B Remote READY
X1010 Main A/D converter module CH1 A/D conversion completed flag
X1011 Main A/D converter module CH2 A/D conversion completed flag
X1012 Main A/D converter module CH3 A/D conversion completed flag
X101C Main A/D converter module Input signal error detection signal
X101D
Main A/D converter module Maximum value/minimum value reset completed
flag
X1020 Extension A/D converter module CH1 A/D conversion completed flag
NZ2EX2B-60DA4 (RX20 to R2F)
X1021 Extension A/D converter module CH2 A/D conversion completed flag
X1022 Extension A/D converter module CH3 A/D conversion completed flag
X1023 Extension A/D converter module CH4 A/D conversion completed flag
X102C Extension A/D converter module Input signal error detection signal
X102D
Extension A/D converter module Maximum value/minimum value reset
completed flag
X102F External power supply READY flag
Y100A Error clear request flag
NZ2GF2BN-60AD4 (RY0 to RY1F)
Y101D Main A/D converter module Maximum value/minimum value reset request
Y102D
Extension A/D converter module Maximum value/minimum value reset
request
NZ2EX2B-60AD4 (RY20 to RY2F)
W1100 Latest error code
Remote register RWr
W1101 Latest warning code
W1102 Main A/D converter module CH1 Digital operation value
W1103 Main A/D converter module CH2 Digital operation value
W1104 Main A/D converter module CH3 Digital operation value
W110A Main A/D converter module Input signal error detection flag
W110B Main A/D converter module Alert output flag
W1112 Extension A/D converter module CH1 Digital operation value
W1113 Extension A/D converter module CH2 Digital operation value
W1114 Extension A/D converter module CH3 Digital operation value
W1115 Extension A/D converter module CH4 Digital operation value
W111A Extension A/D converter module Input signal error detection flag
W111B Extension A/D converter module Alert output flag