7. Open the "Parameter Processing of Slave Station" window.
Project window [Parameter] [Network Parameter]
[Ethernet/CC IE/MELSECNET] button Select the main A/D
converter module in "List of stations". [CC IE Field Configuration] [Online]
[Parameter Processing of Slave Station]
8. Set "Method selection" to "Parameter write".
9. Set "Write Value". Follow the next steps to set the value:
• Click the title cell of "Initial Value" to select all the items, and copy them.
• Click the title cell of "Write Value" to select all the items, and paste the copy.
• Select the items to be changed, and set new values as described in Initial settings ( Page 158,
Section 9.3 (3)).
10. Click button to write the parameters to the A/D converter module.