227
APPX
A
Appendix 3 Details of Remote Buffer Memory
(28)Module operation information initialization command
This command is used to clear the module operation information stored in the non-volatile memory.
Initialization of the module operation information is permitted provided that a non-volatile memory data error
(module operation information) (error code: 0110H) occurs.
(a) Behavior of module operation information initialization
Setting Module operation information initialization command (address: 1004H) to Commanded (1) allows the
module operation information to be initialized.
(b) Default value
The default value is Not commanded (0).
(c) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name Main A/D converter module Extension A/D converter module
Module operation information initialization
command
1004H
The values of b1 to b15 are fixed to 0.
b0b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1
0000000000 0000 0
0: Not commanded
1: Commanded
Completed
(1)
Not performed (0)
Not
performed (0)
Commanded (1)
Not
commanded (0)
Not
commanded (0)
Default values
Module operation
information
Controlled by the program
Module operation information
initialization completed
(address: 1005H)
Module operation information
initialization command
(address: 1004H)
Content of module operation
information error
Controlled by the A/D converter module