TROUBLESHOOTING
12.2 Troubleshooting Flowchart
12.2.4 When the "ALIVE" LED does not turn on or turns off
12 - 7
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
12.2.4 When the "ALIVE" LED does not turn on or turns off
This section describes the troubleshooting for when the "ALIVE" LED of the CPU module
does not turn on at power-ON of the programmable controller or when the "ALIVE" LED
turns off during operation.
(1) Flowchart for when the "ALIVE" LED of the CPU module does not turn on at
power-ON of the programmable controller.
The "ALIVE" LED does not turn on.
Set the RUN/STOP/RESET switch to the
STOP position. If it is impossible to set it at
STOP position, failure of the CPU module is
suspected.
Please consult your local Mitsubishi service
center or representative, explaining a
detailed description of the problem.
RESET position
Possible
STOP/RUN position
Impossible
How is the "ALIVE" LED
of the CPU module?
How is the "POWER"
LED of the power supply
module?
Off
Off
On
On
Check the wiring and turn on all power
supplies.
Execute PLC diagnostics and
troubleshooting according to its result.
Hardware failure of the power supply module
before replacement is suspected.
Hardware failure of the following modules
1) CPU module
2) Base unit
3) CC-Link Safety master module
4) Network module (if mounted)
Execute operation check sequentially from
the minimum system.
For the module that does not operate, please
consult your local Mitsubishi service center or
representative, explaining a detailed
description of the problem.
Replace the power supply module and
check that the "POWER" LED is on.
Can the CPU module
communicate with GX
Developer?
Is RUN/STOP/RESET
switch of the CPU
module set at RESET
position?

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC and is the answer not in the manual?

Mitsubishi MELSEC Specifications

General IconGeneral
CategoryProgrammable Logic Controller (PLC)
ManufacturerMitsubishi Electric
SeriesMELSEC
Programming LanguagesLadder Diagram (LD), Function Block Diagram (FBD), Structured Text (ST), Instruction List (IL), Sequential Function Chart (SFC)
Communication ProtocolsEthernet, CC-Link, RS-232, RS-485, USB, Profibus, Modbus
Model SeriesFX, Q, L, iQ-R, iQ-F
Input Voltage100-240V AC, 24V DC (varies by model)
Memory CapacityVaries widely depending on the CPU module and series. Ranges from kilobytes to megabytes.
I/O Points16 to 8192 points (varies by model)
Communication PortsEthernet, RS-232, RS-485, USB (varies by model)
Programming SoftwareGX Works2, GX Works3, GX Developer
Operating Temperature0°C to 55°C
Storage Temperature-25°C to 75°C
Humidity5% to 95% (non-condensing)
Vibration Resistance10 to 57Hz, 0.075mm amplitude; 57 to 150Hz, 9.8m/s² acceleration
Shock Resistance147m/s², 3 times in each direction (X, Y, Z)
Protection ClassIP20 (varies by model)
CPU Processing Speed0.02μs to 0.1μs per instruction (varies by model)