TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 39
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3102
The network module detected an
error in Network parameter.
The MELSECNET/H inherent
parameter setting is incorrect.
Correct the parameter setting and write
Network parameter to the CPU If an
error occurs even after correction, a
hardware failure is considered. (Please
consult your local Mitsubishi
representative.)
QS
3103
The number of modules actually
mounted is different from that is set in
Network parameter for Ethernet.
The start I/O number of the module
actually mounted is different from that
is set in Network parameter for
Ethernet.
Check the setting in Network
parameter and actual mounting
status, and if they differ, correct either
the setting or mounting status so that
they become the same. If the
parameter setting is corrected, write
Network parameter to the CPU
module.
If an error occurs even after
correction, a hardware failure is
considered. (Please consult your
local Mitsubishi representative.)
QS
3104
The same network number is used for
Ethernet, CC-Link IE controller
network, and MELSECNET/H.
The network number, station number,
and/or group number set in Network
parameter are out of the setting
range.
The specified I/O number is outside
the range of the used CPU module.
The Ethernet inherent parameter
setting is incorrect.
Correct the parameter setting and
write Network parameter to the CPU
module.
If an error occurs even after
correction, a hardware failure is
considered. (Please consult your
local Mitsubishi representative.)
QS
3105
Though the number of CC-Link
modules set in the network
parameters is one or more, the
number of actually mounted modules
is zero.
The start I/O number in the common
parameters is different from that of
the actually mounted module.
The station type of the CC-Link
module count setting parameters is
different from that of the actually
mounted station.
Correct and write the network
parameters.
If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
QS
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC and is the answer not in the manual?

Mitsubishi MELSEC Specifications

General IconGeneral
CategoryProgrammable Logic Controller (PLC)
ManufacturerMitsubishi Electric
SeriesMELSEC
Programming LanguagesLadder Diagram (LD), Function Block Diagram (FBD), Structured Text (ST), Instruction List (IL), Sequential Function Chart (SFC)
Communication ProtocolsEthernet, CC-Link, RS-232, RS-485, USB, Profibus, Modbus
Model SeriesFX, Q, L, iQ-R, iQ-F
Input Voltage100-240V AC, 24V DC (varies by model)
Memory CapacityVaries widely depending on the CPU module and series. Ranges from kilobytes to megabytes.
I/O Points16 to 8192 points (varies by model)
Communication PortsEthernet, RS-232, RS-485, USB (varies by model)
Programming SoftwareGX Works2, GX Works3, GX Developer
Operating Temperature0°C to 55°C
Storage Temperature-25°C to 75°C
Humidity5% to 95% (non-condensing)
Vibration Resistance10 to 57Hz, 0.075mm amplitude; 57 to 150Hz, 9.8m/s² acceleration
Shock Resistance147m/s², 3 times in each direction (X, Y, Z)
Protection ClassIP20 (varies by model)