TROUBLESHOOTING
12.3 Error Code List
12.3.8 Error code list (8000 to 9000)
12 - 53
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
8310
The installed product is different from
the specified one by network parameter.
Check that [Model name], [Module
technical version] or [Production
information] of the CC-Link Safety
remote station set in the network
parameter matches the product
information of the relevant CC-Link
Safety remote station.(Refer to the
manual of the CC-Link Safety remote
module for the confirmation.)
QS
8320
The response data cannot be received
during the initial processing of CC-Link
Safety remote station.
Check that the following operations
are not executed.
(1)Switching the operation mode
(2)Writing the program memory to
ROM
(3)Registration/change of the CPU
access password
(4)Initialization of PLC memory
(If executed, this error may occur due
to the increase of the interval between
data communications of CC-Link
Safety.)
When instantaneous power failure
occurs to the supply power, change to
the asynchronous mode or slow down
the speed.
Execute the link test to check the
soundness of transmission path.
Check the setting of transmission
speed.
Check if the setting value of the
Safety refresh monitoring time is
appropriate.
Check if the setting value of the
Safety data monitoring timer is
appropriate.
Check if the setting value of the
Safety data monitoring timer is
appropriate.
QS
8321
The response data cannot be received
during the normal communication with
CC-Link Safety remote station.
QS
8322
The response data cannot be received
during processing error information
from CC-Link Safety remote station.
QS
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC and is the answer not in the manual?

Mitsubishi MELSEC Specifications

General IconGeneral
CategoryProgrammable Logic Controller (PLC)
ManufacturerMitsubishi Electric
SeriesMELSEC
Programming LanguagesLadder Diagram (LD), Function Block Diagram (FBD), Structured Text (ST), Instruction List (IL), Sequential Function Chart (SFC)
Communication ProtocolsEthernet, CC-Link, RS-232, RS-485, USB, Profibus, Modbus
Model SeriesFX, Q, L, iQ-R, iQ-F
Input Voltage100-240V AC, 24V DC (varies by model)
Memory CapacityVaries widely depending on the CPU module and series. Ranges from kilobytes to megabytes.
I/O Points16 to 8192 points (varies by model)
Communication PortsEthernet, RS-232, RS-485, USB (varies by model)
Programming SoftwareGX Works2, GX Works3, GX Developer
Operating Temperature0°C to 55°C
Storage Temperature-25°C to 75°C
Humidity5% to 95% (non-condensing)
Vibration Resistance10 to 57Hz, 0.075mm amplitude; 57 to 150Hz, 9.8m/s² acceleration
Shock Resistance147m/s², 3 times in each direction (X, Y, Z)
Protection ClassIP20 (varies by model)
CPU Processing Speed0.02μs to 0.1μs per instruction (varies by model)

Related product manuals