Page #155 background imageLoading...
Page #155 background image
12
TROUBLESHOOTING
12.3 Error Code List
12.3.8 Error code list (8000 to 9000)
12 - 55
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
8330
The received command differs from the
expected value.
Check the cable status visually or by
a line test.
Hardware error of the CC-Link Safety
master module or the relevant CC-
Link Safety remote module (Contact
your local Mitsubishi representative.)
QS
8331
Lapse in separated receiving data has
occurred.
QS
8332
The link ID in receiving data is different
from the expected value.
Check if the link ID setting of the
relevant remote station and the link
ID that has been set in the network
parameter are identical.
Hardware error of the CC-Link Safety
master module or the relevant CC-
Link Safety remote module (Contact
your local Mitsubishi representative.)
QS
8333
The running No. in receiving data is
different from the expected value.
Check if the setting value of the
Safety refresh monitoring time is
appropriate.
Hardware error of the CC-Link Safety
master module or the relevant CC-
Link Safety remote module (Contact
your local Mitsubishi representative.)
QS
8334
The CC-Link Safety master station
cannot recognize the separated data.
Check the cable status visually or by
a line test.
Hardware error of the CC-Link Safety
master module or the relevant CC-
Link Safety remote module (Contact
your local Mitsubishi representative.)
QS
9000
Annunciator (F) was set ON
(**** in the error message indicates the
detected annunciator number.)
Read the individual information of the
error using the GX Developer, and
check the program corresponding to the
numerical value (annunciator number).
QS
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC and is the answer not in the manual?

Mitsubishi MELSEC Specifications

General IconGeneral
CategoryProgrammable Logic Controller (PLC)
ManufacturerMitsubishi Electric
SeriesMELSEC
Programming LanguagesLadder Diagram (LD), Function Block Diagram (FBD), Structured Text (ST), Instruction List (IL), Sequential Function Chart (SFC)
Communication ProtocolsEthernet, CC-Link, RS-232, RS-485, USB, Profibus, Modbus
Model SeriesFX, Q, L, iQ-R, iQ-F
Input Voltage100-240V AC, 24V DC (varies by model)
Memory CapacityVaries widely depending on the CPU module and series. Ranges from kilobytes to megabytes.
I/O Points16 to 8192 points (varies by model)
Communication PortsEthernet, RS-232, RS-485, USB (varies by model)
Programming SoftwareGX Works2, GX Works3, GX Developer
Operating Temperature0°C to 55°C
Storage Temperature-25°C to 75°C
Humidity5% to 95% (non-condensing)
Vibration Resistance10 to 57Hz, 0.075mm amplitude; 57 to 150Hz, 9.8m/s² acceleration
Shock Resistance147m/s², 3 times in each direction (X, Y, Z)
Protection ClassIP20 (varies by model)
CPU Processing Speed0.02μs to 0.1μs per instruction (varies by model)