TROUBLESHOOTING
12.4 Canceling Errors
12 - 57
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
When multiple enunciators(F) detected are canceled, the first one with No. F only is
canceled.
If the canceling of errors is performed when multiple continuation errors are occurring,
the LED indication and error information of the CPU module operate as follows.
Refer to the following manual for details of error canceling.
QSCPU User's Manual (Function Explanation, Program Fundamentals)
POINT
1. When the error is canceled with the error code to be canceled stored in the
SD50, the lower one digit of the code is neglected.
(Example)
If error codes 2100 and 2106 occur, and error code 2100 to cancel error
code 2106.
If error codes 2100 and 2125 occur, error code 2125 is not canceled even if
error code 2100 is canceled.
2. Errors developed due to trouble in other than the CPU module are not
canceled even if the special relay (SM50) and special register (SD50) are
used to cancel the error.
(Example)
Since "INTELLIGENT FUNCTION MODULE DOWN" is the error that
occurred in the base unit, intelligent function module, etc. the error cause
cannot be removed even if the error is canceled by the special relay (SM50)
and special register (SD50).
Refer to the error code list and remove the error cause.
Error Canceling Status
LED Indication *1
("ERR." LED, "BAT." LED,
"USER" LED)
Error Information
(SM0, SM1, SM5, SM16, SD0
to 26)
Before canceling errors On
The error information of the
continuation error that
occurred last is stored.
The error which occurred last
is cancelled.
(The continuation error that is
not canceled remains.)
On
Returned to the status without
error.
Errors other than the
continuation error that
occurred last are cancelled.
(The continuation error that is
not canceled remains.)
On
No change
(The error information that
occurred last is retained.)
All the continuation errors are
cancelled.
Off No error
*1: 1) Error code: When 1600 (BATTERY ERROR) occurs, only "BAT." LED turns on.
Error code: When canceling the error code 1600, "BAT." LED turns off.
2) Error code: When 9000 (F****) occurs, only "USER" LED turns on.
Error code: When canceling the error code 9000, "USER" LED turns off.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC and is the answer not in the manual?

Mitsubishi MELSEC Specifications

General IconGeneral
CategoryProgrammable Logic Controller (PLC)
ManufacturerMitsubishi Electric
SeriesMELSEC
Programming LanguagesLadder Diagram (LD), Function Block Diagram (FBD), Structured Text (ST), Instruction List (IL), Sequential Function Chart (SFC)
Communication ProtocolsEthernet, CC-Link, RS-232, RS-485, USB, Profibus, Modbus
Model SeriesFX, Q, L, iQ-R, iQ-F
Input Voltage100-240V AC, 24V DC (varies by model)
Memory CapacityVaries widely depending on the CPU module and series. Ranges from kilobytes to megabytes.
I/O Points16 to 8192 points (varies by model)
Communication PortsEthernet, RS-232, RS-485, USB (varies by model)
Programming SoftwareGX Works2, GX Works3, GX Developer
Operating Temperature0°C to 55°C
Storage Temperature-25°C to 75°C
Humidity5% to 95% (non-condensing)
Vibration Resistance10 to 57Hz, 0.075mm amplitude; 57 to 150Hz, 9.8m/s² acceleration
Shock Resistance147m/s², 3 times in each direction (X, Y, Z)
Protection ClassIP20 (varies by model)
CPU Processing Speed0.02μs to 0.1μs per instruction (varies by model)