12 - 66
12.5 Error codes returned to request source during communication with CPU module
12
TROUBLESHOOTING
Table12.9 Error code (Continue)
Error code
(Hexadecimal)
Error item Error details Corrective action
42B9
H
General data
frame error
The communication data whose format is not
supported by the transfer target CPU has
been sent.
Check whether the application compatible with the
QS001CPU is used or not.
4B00
H
Target-related
error
An error occurred in the access destination or
relay station, or the specified transfer setup
(request destination module I/O number) is
illegal.
Take corrective action after checking the error that
occurred at the specified access destination or the
relay station to the accessed station.
Check the transfer setup (request destination module
I/O number or PLC number) in the request data of the
peripheral device.
4B02
H
The request is not addressed to the CPU
module.
Perform operation for the module that can execute the
specified function.
4B03
H
The specified route is not supported by the
specified CPU module version.
Check whether the specified route is supported or not.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC and is the answer not in the manual?

Mitsubishi MELSEC Specifications

General IconGeneral
CategoryProgrammable Logic Controller (PLC)
ManufacturerMitsubishi Electric
SeriesMELSEC
Programming LanguagesLadder Diagram (LD), Function Block Diagram (FBD), Structured Text (ST), Instruction List (IL), Sequential Function Chart (SFC)
Communication ProtocolsEthernet, CC-Link, RS-232, RS-485, USB, Profibus, Modbus
Model SeriesFX, Q, L, iQ-R, iQ-F
Input Voltage100-240V AC, 24V DC (varies by model)
Memory CapacityVaries widely depending on the CPU module and series. Ranges from kilobytes to megabytes.
I/O Points16 to 8192 points (varies by model)
Communication PortsEthernet, RS-232, RS-485, USB (varies by model)
Programming SoftwareGX Works2, GX Works3, GX Developer
Operating Temperature0°C to 55°C
Storage Temperature-25°C to 75°C
Humidity5% to 95% (non-condensing)
Vibration Resistance10 to 57Hz, 0.075mm amplitude; 57 to 150Hz, 9.8m/s² acceleration
Shock Resistance147m/s², 3 times in each direction (X, Y, Z)
Protection ClassIP20 (varies by model)
CPU Processing Speed0.02μs to 0.1μs per instruction (varies by model)