Selecting PT1 CALIBRATION
displays the check/edit screen for
the typical reading of PT1 probe at
130.4°C.
This value is indicated directly on
PT1 probe.
If the PT1 probe is replaced,
proceed as follows:
- note typical reading of new probe
- activate setup system by
pressing OK
- change reading using + / - as
required
- press OK/ENTER to confirm
The system allows a maximum
variation range of +/- 10 ohm with
respect to a nominal reading of
1500 ohm at 130.4°C.