Scenarios
The Override button can be pressed when all of the following
conditions are satised.
IMM is in manual mode; e.g., the Automatic Mode input signal is 0.
The Machine OK signal is 1.
The console is in Run, Standby, or Startup mode.
The alarm severity is less than a fault; i.e., none of T/C, Triac,
Fuse, Power Limit, Ground errors.
When the Override button is pressed, the Enable Mould Closure signal
will stay active for the time entered in the Override Time setting.
After the timer elapses, the Enable Mould Closure signal becomes
inactive.
If the Override button is pressed while an override is active, the
override time remaining is set to the length of time in the Override
Time setting.
Override is canceled when any of the following conditions are
satised.
The console mode is changed.
The Automatic Mode signal is received from the IMM.
The machine OK signal is lost.
Override is NOT canceled when
switching from Run to Standby mode when it is done automatically
from the delay of the automatic mode signal being switched to 0,
or
there is a severe alarm; e.g., none of T/C, Triac, Fuse, Power
Limit, Ground errors.
4-44
© 2021 Mold-Masters (2007) Limited. All Rights Reserved.