IP67 IO-Link Modules for EtherNet/IP
LEDs and status bits
The table below shows the LEDs state according to power supply voltages applied and the corresponding
status bits.
Input Process data -
Status bit
State & Power supply voltages
Voltage not present (UL=0 V)
If no DO configured
Powered and UB not powered
Voltage not present (UL=0 V)
• If DO configured & energized
• Hub 12/4 configured with PIN 2 used as
auxiliary power
Voltage present 19.2 V ≤ UL ≤ 30 V
Voltage < 11 V
• If UB < 11V, HarshIO will shutdown
• If UB > 13V, HarshIO will boot up
Voltage present 19.2 V ≤ UL ≤ 30 V
(*): a ratio is applied on 8A. The real threshold is 8A x1.45
UVx: Under Voltage (x = UL or UB)
OVx: Over Voltage (x = UL or UB)
OLx: Over Load (x = UL or UB)
DO: Digital Output configured on Pin2
Note!
As IO-Link operation voltage is defined above 18V, IO-Link communication will be
reinitialized if UB goes down under 17V and comes back up to 19.2V.