IP67 IO-Link Modules for EtherNet/IP
4. Apply Power
Switch on the power supply module and observe the LEDs status indicator.
If the module is correctly wired, then the following LEDs status indicator should be:
Logic/Communications/sensor voltage present
DI is not set / D0 is not energized
SIO/ IO-link channel is not activated.
IP address assigned by DHCP server.
Wait for an IO connection
No diagnostic/default in progress
Note!
The result above is applicable if there is no EtherNet/IP connection between the
EtherNet/IP scanner and the HarshIO module.
Rockwell Studio 5000
We provide multiple materials for a better integration of the HarshIO module into Studio 5000 from this link:
- The technical note “Getting started with RS Studio5000”.
- AOI (Add-On-Profile) with the associated the technical note as well as sample ladder code to send IO-
Link command via CIP explicit message (AOI also imported)
- EDS file