HarshIO 600 eIP
54
IP67 IO-Link Modules for EtherNet/IP
Note!
If the PLC sends an ISDU request to write param GHI, the HarshIO module will not
restore param ABC. In such case, and to align param, the user will force a restore
(Force restore ISDU request) if param ABC must be downloaded to the Molex IO-Link
hub or force a backup (Force backup ISDU request) if param GHI must be uploaded
and stored into the DS file.
IO-Link
communication
OK
Param DEF
Param ABC
Param ABC