EasyManua.ls Logo

Moog G394-030

Moog G394-030
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
moog
MSD Servo Drive Compact Operation Manual
23
[ Installation ]
to the glossaryto the table of contents
Id no.: CA97555-001, Rev. 3.0 - Date: 0 6/2012
DANGER FROM ELECTRICAL TENSION! Danger to life! Never wire or
disconnect electrical connections while these are live. Always disconnect the
power before working on the device. Dangerously high voltages of ≥50V
may still be present 10 minutes after the power is cut (capacitor charging). So
always check that the power has been cut.
ATTENTION! If local regulations require the installation of a residual current
operated protective device, the following applies: In case of a fault the drive
is able to generate d.c. leak currents without zero crossing. Drives therefore
must only be operated with (RCDs)
1)
type B for a.c. fault currents, pulsating
or smooth d.c. fault currents, which are suitable for servo drive operation, see
IEC60755. RCMs
2)
can additionally be used for monitoring purposes.
1) Residual current protective device
2) Residual current monitor
Note the following points:
• Switching the mains power:
In case of too frequent switching the unit protects itself by high-resistance
isolation from the system. After a rest phase of a few minutes the device is
ready to start once again.
• TN and TT network: Operation is permitted if:
in the case of single-phase devices for 1 x 230 V AC the supply system
conforms to the maximum overvoltage category III as per EN61800-5-1.
in the case of three-phase devices with external conductor voltages
3x230VAC, 3x400VAC, 3x460VAC and 3x480VAC
1. the neutral point of the the supply system is grounded and
2. the supply system conforms to the maximum overvoltage category III
as per EN61800-5-1 at a system voltage (external conductor neutral
point) of maximum 277V.
• IT network: not permitted!
In case of an ground fault the electrical stress is approx. twice as high.
Clearances and creepages to EN61800-5-1 are no longer maintained.
!
• Connection of the servo drives by way of a mains choke is mandatory:
where the drive is used in applications with disturbance variables
corresponding to environment class 3, as per EN 61000-2-4 and above (hostile
industrial environment)
in the case of single-phase mains supply
for compliance with EN61800-3 or IEC61800-3
• For further information on permissible current loads, technical data and ambient
conditions please refer to the appendix.
NOTE: Please be aware that the MSDServoDriveCompact is not rated
for environment class 3. Further measures are essential in order for that
environment class to be attained! For further information please consult your
project engineer.
Drive
Device connected load
1)
[kVA]
Maximum
cable cross-
section [mm²]
Specified mains fuse,
duty class [A]
with mains
choke (4% u
K
)
without
mains choke
G394-030 1.3 1.6
2.5
1xmaximum 16 (1-phase)
3xmaximum 16 (3-phase)
G394-020 1.5 1.9 3xmaximum 6
G394-059 2.6 3.2
2.5
1xmaximum 16 (1-phase)
3xmaximum 16 (3-phase)
G394-035 2.7 3.3 3xmaximum 10
G394-080 3.5 4.3
4
1xmaximum 20 (1-phase)
3xmaximum 20 (3-phase)
G394-065 5.0 6.1 3xmaximum 16
1) At 3x230VAC or 3x400VAC mains voltage
2) The minimum cross-section of the mains power cable depends on the local regulations and conditions, as well as on the
rated current of the drive.
Table 3.4 Connected load and mains fuse

Table of Contents

Related product manuals