Leakage current
excceds the limit.
1. Check the wire and panels
which may cause the leakage.
2. If the error message still
remains, please contact your
installer.
The resistance
between PV and
ground is too low.
1. Restart the inverter.
2. If the error message still
remains, please contact your
installer.
Please contact your installer.
Battery high voltage
fault
Battery voltage
exceeds the limit.
1. Check the battery voltage.
2. If the error message still
remains, please contact your
installer.
The inverter is
loaded with more
than 110% load and
time is up.
Reduced the connected load
by switching off some
equipment.
Check if wiring is connected
well and remove abnormal
load.
Please contact your installer.
Internal
components failed.
1. Restart the inverter.
2. If the error message still
remains, please contact your
installer.
Internal
components failed.
Please contact your installer.
Internal
components failed.
Please contact your installer.
Grid connects to
output terminal.
Don’t connect the grid to the
ouput terminal.
Short circuit on PV
input
Short circuited on
PV input
Please contact your installer.
RS inverter short
circuit
Short circuited on
RS inverter
Check if all wiring is connected
well and remove abnormal
loads.
ST inverter short
circuit
Short circuited on
ST inverter
Check if all wiring is connected
well and remove abnormal
loads.
TR inverter short
circuit
Short circuited on
TR inverter
Check if all wiring is connected
well and remove abnormal
loads.