EasyManua.ls Logo

MSA GM FL5000 - Page 32

MSA GM FL5000
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32 FL5000 Multi-Spectrum Flame Detector US
5 Installation
5.6.8 Analog Output
Terminal Block Connection Point Block Name Setting
P1 Term 7 0 - 20 mA Analog Output
The 0 to 20 mA output is a current signal that corresponds to the following:
Analog Output HART (1.25 mA)* HART (3.5 mA) HART Disabled/OFF
Startup 1.25 mA 3.5 mA 0 to 0.2 mA
FAULT Signal 1.25 mA 3.5 mA 0 to 0.2 mA
Test Mode 1.5 mA 3.5 mA 1.5 ± 0.2 mA
COPM Fault Signal 2.0 mA 3.5 mA 2.0 ± 0.2 mA
Ready Signal 4.05 ± 0.2 mA 4.05 ± 0.2 mA 4.05 ± 0.2 mA
INSTANT ALARM Signal 16.0 ± 0.2 mA 16.0 ± 0.2 mA 16.0 ± 0.2 mA
SUSTAINED ALARM Signal 20.0 ± 0.2 mA 20.0 ± 0.2 mA 20.0 ± 0.2 mA
Bluetooth Load 3.0 mA 3.0 mA 3.0 mA
* HART (1.25 mA) is the default.
NOTE: Refer to the FL5000 Modbus or HART manual for Current Range selection.
The maximum analog output load is 600 Ω.
The COPM Fault Signal may also be set to 0 mA at the factory (non HART only).
Startup mode lasts exactly 15 seconds.
5.6.9 Cable Requirements
0 - 20 mA
For interfacing with 250 Ω input impedance devices,
the following maximum cable lengths apply (maximum
50 Ω loop):
AWG Feet Meters
14 4,500 1,370
16 2,340 715
18 1,540 470
20 970 300
22 670 205
NOTE: When Ex d cable glands are utilized, shielded cable must also be used.

Related product manuals