• The other wire within the cable is not used.
• It is unnecessary to connect wire to the other terminal
positions within the remote sensor.
• Do not connect the shield at the remote sensor.
4. Screw the conduit or cable grip or gland into the conduit
opening. Relieve any excess slack in the cable.
5. Re-install the cover on the Toxgard II Remote Sensor.
"
WARNING
Do not let the cover remain off of an explosion-proof Toxgard II
Sensor. Since a source of ignition is exposed, an explosion may
occur if a metal object contacts the circuitry and produces sparks
in an atmosphere of combustible gas.
Toxic Gas Remote Sensor Wiring
(FIGURE 1-11)
Fifty feet of six-conductor cable is supplied with the unit.
• This cable has a connector on one end which plugs into its
mate within the Toxgard II Monitor/Less Sensor.
• The other end of the cable can be cut to the exact
length needed.
• Do not run more than 50 feet of cable or splice on
additional cable.
At the Toxgard II Monitor/Less Sensor Location
The cable connects to J5 at the upper right portion of the (lower)
main pc board.
Figure 1-11.
Toxic Gas Remote Sensor Cable
Chapter 1, Set-up