12. For Toxic or Oxygen Remote Sensor Toxgard II Gas
Monitors:
Re-connect the sensor wiring on the termination printed circuit
board in the module by aligning the connector and
inserting it into J1 (FIGURE 1-8).
For Combustible Remote Sensor Toxgard II Gas Monitor:
Re-connect the sensor wiring onto the wiring termination
printed circuit board in the module (FIGURE 1-7).
13. Re-install the cover of the Remote Sensor Toxgard II
Gas Monitor.
"
WARNING
Do not let the cover remain off of an explosion-proof Remote Sensor
Toxgard II Gas Monitor. Since a source of ignition is exposed, an
explosion may occur if a metal object contacts the circuitry and
produces sparks in an atmosphere of combustible gas.
14. Locate the Remote sensor Toxgard II Gas Monitor base
plate and two #10-32 screws and lock washers.
15. Remove the four screws holding the module mounting
bracket (FIGURE A-6).
Figure A-6.
Remote Sensor Base Plate
Appendix A, Optional Toxgard II Duct Mount Kit
A-6