Manual MVK-MP
50 V 3.5
Byte 7 Device-related diagnostic
Undervoltages Sensor & Bus supply
The sensor bus supply of the module is <18V. Connect or increase voltage.
Note line voltage drop and maximum values.
Under Voltage Actuator Supply8
The actuator supply of the module is <18V. Connect or increase voltage. Note
line voltage drop and maximum values.
No Actuator Supply
7
The actuator supply of the module is <12V. Connect or increase voltage. Note
line voltage drop and maximum values.
External Fault
Group diagnostic dependent of channel diagnostics. Correct channel-related
Sensor Short Circuit
Group diagnostic dependent of channel diagnostics. Correct channel-related
Actuator Shutdown
8
Group diagnostic dependent of channel diagnostics. Correct channel-related
Actuator warning8
Group diagnostic dependent of channel diagnostics. Correct channel-related
Analog channel8
Group diagnostic dependent of channel diagnostics. Correct channel-related
Fig. 40: Byte 7 Device-related diagnostic
7
These diagnostics do not exist for input module MVK-MP DI8 (DI8) Art.-No. 55307.
8
The different analog channel diagnostics (e.g. line breaks) are combined in this bit.