Manual MVK-MP
26 V 3.5
4. Setup
4.1 Assigning and Setting the Profibus Address
The Profibus address is set by means of two BCD switches directly on the MVK-MP. Allowable values
are between 0 and 99. Usually, the addresses 0 to 2 are assigned to the DP master. Therefore, we
recommend setting the addresses for the MVK-MP starting with address 3.
The preset address will be read in after the supply voltage is connected. Therefore,
a change of the address will only become effective after a voltage reset of the
module.
When assigning the address it must be ensured that each Profibus device gets a
clear and individual address.
4.2 GSD File
The operation of the equipment described in this manual requires a GSD file
MURR064A.* for digital modules
MURR09AD.* for analog modules
MURR09EB.* for safety module
The suffix of the file indicates the language version. The GSD files are available in six languages.
Language
Suffix
*.gsd
Default = English
*.gse
English
*.gsg
German
*.gss
Spanish
*.gsf
French
*.gsi
Italian
*.gsp
Portuguese
Tab. 1: GSD Files
The GSD file can be downloaded from the Murrelektronik homepage:
www.murrelektronik.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Murr Elektronik MVK-MP and is the answer not in the manual?