EasyManua.ls Logo

Murr Elektronik MVK-MP - Specific Module Error Displays

Murr Elektronik MVK-MP
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual MVK-MP
44 V 3.5
5.2.1 MVK-MP DO4 (DO4) DI4 (DI4) Art.-No. 55274
Error
LED on M12 socket
No. x
Error
Power
Channel 0x
Channel 1x
U
A
U
S
U
A
U
S
Undervoltage bus & sensor
supply
Red
Undervoltage actuator supply
Red
Bus&sensor supply ≤12V
Red
Off
No actuator supply
Red
Off
External fault (socket 4 … 7)
Red
Short-circuit (socket 4 … 7)
Red
Actuator shutdown (socket 03)
Red
Red
Actuator warning (socket 0 … 3)
Red
Red
Tab. 21: Error displays MVK-MP DO4 (DO4) DI4 (DI4) Art.-No. 55274
5.2.2 MVK-MP DO8 (DO8) Art.-No. 55290
Error
LED on M12 socket
No. x
Error
Power
Channel
0x
Channel
1x
U
A
U
S
U
A
U
S
Undervoltage bus supply
Red
Undervoltage actuator supply
Red
Bus supply ≤12V
Red
Off
No actuator supply
Red
Off
Actuator shutdown
Red
Red
Actuator warning
Red
Red
Tab. 22: Error displays MVK-MP DO8 (DO8) Art.-No. 55290
5.2.3 MVK-MP K3 DO4 (DO4) / DIO4 (DIO4) Art.-No. 55291
Status
Power
Error
Power
U
A1
U
A2
U
S
U
A
U
S
U
A
Bus & sensor supply OK (18V)
Green
UA actuator supply OK (18V)
Green
Bus & sensor supply 18V
Red
UA actuator supply 18V
Red
Bus & sensor supply 12V
Red
Off
No UA actuator supply (12V)
Off
UA1 actuator supply OK (18V)
Green
UA2 actuator supply OK (18V)
Green
No UA1 actuator supply (12V)
Off
No UA2 actuator supply (12V)
Off
Tab. 23: Status displays MVK-MP K3 DO4 (DO4) / DIO4 (DIO4) Art.-No. 55291