uPASS Target | installation guide
30/
42
6.4.3 Relay / timing
Configure relay output and timing parameters.
Figure 27: Relay / timing settings
Enable 'Automatic relay activation' to activate the relay upon identification. When disabled, the relay can only be
activated manually trough a serial command or digital input activation.
The 'Tag hold time' setting is the minimum time a tag is remembered. During this time the front cover LED indicates a
tag read and the relay is switched.
The 'Vehicle hold time' setting is the time, after a vehicle-id tag has been found, for which the reader will search for
driver-id tags. This setting is only used in the Nedap DUAL-ID mode.
The (random) RF off time parameter can be used to enable multiple Nedap uPASS readers on the same frequency
without then interfering with each other. By default this setting is on, it is recommended to keep this setting on.
OSDP firmware
Use the OSDP_OUT command to control the relay output state. The output allow for direct activation and deactivation
plus timed operation (OSDP output control compliance level 3). The permanent command is volatile (does not
transcend power cycles).
When the status of the relay output changes the reader will send an output status change report message
OSDP_OSTATR.