8 Additional information
BU 0155 en-3520 103
8.1.2 EMC evaluation - EN 55011-1 (environmental standard)
The limits are defined in dependence on the basic environment in which the product is operated in this
standard. A distinction is made between 2 environments, whereby the 1st environment describes the
non-industrial living and business area without its own high-voltage or medium-voltage distribution
transformers. The 2nd environment, on the other hand, defines industrial areas which are not
connected to the public low-voltage network, but have their own high-voltage or medium-voltage
distribution transformers. The limits are subdivided into classes A and B.
Limit class in accordance with EN 55011
B
A
Operation permissible in
1. Environment (living environment)
X
-
2. Environment (industrial environment)
X
X
1)
Note required in accordance with EN-61800-3
-
2)
Sales channel
Generally available
Limited availability
EMC situation
No requirements
Installation and start-up by EMC expert
1)
Device used neither as a plug-in device nor in moving equipment
2) "The drive system is not intended for use in a public low-voltage network that feeds residential areas".
Table 7: EMC - Limit class in accordance with EN 55011