NORDAC LINK (SK 155E-FDS / SK 175E-FDS)Users Manual for Motor Starters as Field Distributors
44 BU 0155 en-3520
2.3.3.1 Control connection details
Meaning, Functions
Description / Technical data
Contact
Parameter
(designation)
Meaning
No.
Function of factory setting
Digital outputs
Signalling of the operating statuses of the FI
according to EN 61131-2
24 V DC
With inductive loads: Provide protection
via free-wheeling diode!
Maximum load 50 mA
DOUT1 Digital output 1 P434 [-01] No function
DOUT2
Digital output 2
P434 [-02]
No function
Digital inputs
Actuation of device using an external controller, switch or similar.
The factory settings of digital inputs DIN1 to DIN3 depend on the configuration of
option slots H1 and H2.
DIN1-5 according to EN 61131-2, type 1
Low: 0-5 V (~ 9.5 kΩ)
High: 15-30 V (~ 2.5 - 3.5 kΩ)
Scan time: 1 ms
Reaction time: 4 ms
Input capacitance: 10 nF
DIN1
Digital input 1
P420 [-01]
No function
DIN2 Digital input 2 P420 [-02] No function
DIN3
Digital input 3
P420 [-03]
No function
BDI1
Digital input 4
P420 [-09]
No function
BDI2
Digital input 5
P420 [-10]
No function
PTC resistor input
Monitoring of motor temperature using PTC
The motor´s PTC resistor (TF) is
connected via the Q8 motor connection.
Use a shielded cable.
Connect a temperature sensor to put the device into operation
mode. As an alternative, you can deactivate the input
function. In this case, however, the thermal monitoring of the
motor is no longer possible.
TF+
PTC resistor input +
P425 On
TF-
PTC resistor input -
Control voltage source
Control voltage from the inverter, e.g. as power supply for accessories
24 V DC ± 25 %, short circuit-proof
Maximum load
1)
VO / 24V
Voltage output
-
-
GND / 0V
Reference potential GND
-
-
1) See "Total currents" information ( Section )
Control voltage
connection
Supply voltage for the FI
24 V DC ± 25 %
200 mA … 800 mA, depending on load of
inputs and outputs and use of options
With option (-HVS): Automatic changeover between the
external supply via the connection plug and internal mains
unity if the connected control voltage is insufficient.
24V
Voltage input
-
-
GND / 0V
Reference potential GND
-
-
Brake actuation
Connection and actuation of an electromechanical brake. The FI generates an
output voltage for this, which depends on the mains voltage. The assignment of the
correct brake coil voltage must be taken into account in the selection.
Connected loads:
( Section )
Current: ≤ 500 mA
Permissible switching cycle time:
to 150 Nm ≤ 1/s
to 250 Nm ≤ 0.5/s
BR+
Brake control
P107/114
0 / 0
BR-
Brake control