4 Commissioning
BU 0155 en-3520 51
4.2 Starting up the device
The motor starter may be commissioned in various ways:
a)
For simple applications (e.g. conveyor applications) via the DIP switches and potentiometers
accessible via the option slots E1 – E3.
b) By parameter adjustments via the control and parameterisation units (SK CSX-
SK PAR-3H), NORDAC ACCESS BT using the NORDCON APP or PC-
software.
Pay attention to the setting of parameter P130
. The parameter settings only take effect if
P130 = 1.
After the
of the motor starter, the parameter values from the RAM memory
must be transferred to the device’s flash memory (
P550). Otherwise, the settings made will
be lost upon shutdown of the device.
Flash memory note: Approximately 100 memory cycles are possible.