5.2.1 Operating displays
P001 Selection of display value RM
Setting range
0 … 11
Other applicable parameter(s): P000
Factory setting
{ 0 }
Description
Selection of the operating value to be displayed (see P000)
Setting values
Value Meaning
0 Actual frequency [Hz]
Output frequency currently being supplied by device
1 Nominal frequency [Hz]
Frequency of mains voltage that is currently present
2
Current
[A]
Current output current measured by device
3
Effective current
[A]
Effective current currently being supplied by device
4 Reactive current [A]
Reactive current currently being supplied by device
5 Mains voltage [V]
Voltage currently being measured at the input terminals
6
cos Phi
[-]
Calculated value of current power factor
7
Apparent power
KVA
Calculated value of current apparent power
8 Effective power [kW]
Calculated value of current effective power
9
Mains phase sequence
[-]
0 = Clockwise rotating field
1 = Counter-Clockwise rotating field
10
Duty factor
[%]
Phase angle control value currently being achieved by device.
0 % = "Motor off", 100 % = "Motor voltage = Mains voltage"
11
Actual current
amplification
[%]
Actual measured current in relation to the measurement range
P003 Supervisor code RM
Setting range
0 … 9999
Factory setting
{ 1 }
Description
The scope of the visible parameters can be influenced by setting the supervisor code.
Setting values
Value Meaning
0
Supervisor mode off
The supervisor parameters are not visible.
1
Supervisor mode on
All parameters are visible.
2 … Supervisor mode off
The supervisor parameters are not visible.