NORDAC LINK (SK 155E-FDS / SK 175E-FDS) – Users Manual for Motor Starters as Field Distributors
76 BU 0155 en-3520
5.2.1 Operating displays
P001 Selection of display value RM
Other applicable parameter(s): P000
Selection of the operating value to be displayed (see P000)
Value Meaning
0 Actual frequency [Hz]
Output frequency currently being supplied by device
1 Nominal frequency [Hz]
Frequency of mains voltage that is currently present
Current output current measured by device
Effective current currently being supplied by device
4 Reactive current [A]
Reactive current currently being supplied by device
5 Mains voltage [V]
Voltage currently being measured at the input terminals
Calculated value of current power factor
Calculated value of current apparent power
8 Effective power [kW]
Calculated value of current effective power
0 = Clockwise rotating field
1 = Counter-Clockwise rotating field
Phase angle control value currently being achieved by device.
0 % = "Motor off", 100 % = "Motor voltage = Mains voltage"
11
Actual current
[%]
Actual measured current in relation to the measurement range
P003 Supervisor code RM
The scope of the visible parameters can be influenced by setting the supervisor code.
Value Meaning
The supervisor parameters are not visible.
All parameters are visible.
2 … Supervisor mode off
The supervisor parameters are not visible.