4.4.3.4 Addressing
The motor starter is addressed via two 4-pole DIP switch
blocks (S3/ S4). They can be found on option slot E3.
“S4” switch (x1)
Setting the decimal number range from 0 to 9
“S3” switch (x10)
Setting the address’s 10s digit. The 0 to
9 setting
range is linked to the factor 10.
Example
Switch S3 = 4 (0100) ( 4x)
Switch S4 = 2 (0010) ( x2)
Resulting PROFIBUS address = 42
DIP switch encoding
S3 or S4
Value
0000 0
0001 1
0010
2
0011
3
0100 4
0101 5
0110
6
0111
7
1000 8
1001 9
1010
/
1)
1111
1) No function
The motor starter’s PROFIBUS address can be set via the DIP switches in the ranges from 1 to 79
and 81 to 99.
If the addresses 0 or 80 are set, the motor starter interprets these values as address 126.
Communication is not possible.
The address is read directly after switching on the 24 V supply at the motor starter.
A change of address becomes effective only after switching on the 24 V DC voltage supply of the