4 Commissioning
BU 0155 en-3520 55
4.2.2.3 DIP switch (S1, S2)
The rated motor current is set via the DIP switch
(S1).
Basic functions of the motor starter are set via the
DIP switch (S2).
The DIP switches are locat
ed at the option slot
E1.
DIP switch (S1)
Setting the rated motor current
Device type
SK 1x5E-FDS-
DIP switch position
(Setting according to motor name plate)
0000 0001 0010 0011 0100 0101 0110 0111 1000 1001 1010 1011 1100 1101 1110 1111
…111-…
OFF
1)
0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.9 2.2 2.5 2.9 [A]
…301-…
OFF
1)
0.8
1.0
1.2
1.4
1.6
1.9
2.2
2.5
2.9
3.2
3.6
4.8
5.3
6.7
7.0
[A]
1) I
2
t-Monitoring deactivated
DIP switch (S2)
No.
Bit DIP switch (S2)
In delivery state, all four DIP switches are in position “0” (“OFF”).
4/3
2
3/2
Shutdown mode
DIP no.
4
3
0
0
Shutdown mode 1 (factory setting)
I
0
Shutdown mode 2
0
I
Shutdown mode 3
I
I
Shutdown mode 4
2
2
1
Overtemperature motor
(SK 155E)
0
Error message (E002) and shutdown of device in case of
overtemperature
I
Warning message (C002) in case of overtemperature (factory setting)
Phase sequence
detection
(SK 175E)
0
Phase sequence according to mains connection (factory setting)
I
Phase sequence according to required direction of rotation
Automatic detection of phase sequence
1
2
0
Automatic start
0
Edge-controlled (factory setting)
I
Level-controlled
ATTENTION: Drive may start up immediately!