NORDAC LINK (SK 155E-FDS / SK 175E-FDS)Users Manual for Motor Starters as Field Distributors
54 BU 0155 en-3520
4.2.2.2 Potentiometers P1 to P3
Using the potentiometers P1 to P3 (option slot
E2
), basic settings can be made for motor starter
operation. They have a latching design and 10
scale values. The potentiometers have non-linear
characteristic curves on the software side.
(For information on S3 and S4, see Section
4.4.3.4 "Addressing")
Potentiometer P1
Setting the reverse lockout time (see also P570)
Device type
SK 175E-FDS-
Scale value
[s]
…301-…
0
1)
0.2
0.3
0.5
0.7
1.0
1.5
2.0
3.0
5.0
1)
Without reverse lockout time
Potentiometer P2
Setting the initial torque (voltage) (see also P210)
Device type
SK 1x5E-FDS-
Scale value
[%]
…301-…
10
15
20
25
30
35
40
50
70
100
Potentiometer P3
Setting the acceleration and expiration time (see also P102/P103)
Device type
SK 1x5E-FDS-
Scale value
[s]
…301-…
OFF
1)
0.1
0.2
0.3
0.5
0.7
1.0
1.5
2.0
3.0
1)
Soft start deactivated