NORDAC LINK (SK 155E-FDS / SK 175E-FDS) – Users Manual for Motor Starters as Field Distributors
104 BU 0155 en-3520
8.1.3 EMC of device
EMC interference to the environment
This device produces high-frequency interference, which may make additional suppression measures
necessary in domestic environments (see 8.1 "Electromagnetic compatibility (EMC)").
The device is exclusively intended for commercial use. It is therefore not subject to the requirements
of the standard EN 61000-3-2 for radiation of harmonics.
The limit value classes are only achieved if
• the wiring is EMC-compliant
• the length of shielded motor cable does not exceed the permissible limits
If a shielded motor cable is used, the shield of the motor cable must be connected to the motor.
Device version
Max. motor cable length,
shielded
Conducted emissions 150 kHz - 30 MHz
Class A Class B
Standard configuration for
operation on TN/TT networks
(active integrated mains filter)
20 m -
EMC overview of standards that are used in accordance with EN 60947-4-2
as checking and measuring procedures:
-related emission
terference voltage)
EN 55011
(interference field strength)
EN 55011
Interference immunity EN 61000
-6-1, EN 61000-6-2
ESD, discharge of static electricity
EN 61000-4-2 6 kV (CD), 8 kV (AD)
EMF, high frequency electro-magnetic
fields
EN 61000-4-3 10 V/m; 80 – 1000 MHz
Burst on mains and motor cables
Surge (phase-phase / phase-ground)
Cable-led interference due to high
frequency fields
EN 61000-4-6 10 V, 0.15 – 80 MHz
Voltage fluctuations and drops
Voltage asymmetries and frequency
changes
EN 61000-2-4 3 %; 2 %
Table 8: Overview according to product standard EN 60947-4-2