NORDAC LINK (SK 155E-FDS / SK 175E-FDS) – Users Manual for Motor Starters as Field Distributors
96 BU 0155 en-3520
6.3 Messages
Error messages
Display in the
SimpleBox / ControlBox
Fault
Text in the ParameterBox
Cause
• Remedy
Group Details in P700
[-01] / P701
E001 1.0 Overtemp. Thyristor
"Thyristor module
overtemperature"
Temperature monitoring of the thyristor module
Temperature monitoring is performed on the basis of a
calculation model. The error message is triggered if the
results exceed the permissible temperature range.
• Check the ambient temperature
• Reduce the motor load during the acceleration phase
• Check the device for dirt
E002
Ext Resistor Temp
“External braking resistor
overtemperature”
Temperature sensor (e.g. braking resistor) has been
triggered. The digital input is “low”.
• Check connection and temperature sensor.
E003 3.0 I
2
t overcurrent limit
• Continuous overload on the motor
3.3 Thyristor overcurrent • Continuous overload on the motor during
acceleration phase
E004 4.5 Overcurrent / short circuit in
the brake rectifier
Overcurrent / short circuit in the
brake rectifier
• Electromechanical brake defective
• Electromechanical brake connected with
impermissible electrical data
Check the connection data
E005 5.1 Mains overvoltage
Mains voltage is too high
• See technical data ( Section 7)
E006 6.1 Mains undervoltage
• See technical data ( Section 7)
E007 7.0 Mains phase error Error at terminal connection side
• a network phase is not connected
• network is non-symmetrical
E016 16.0 Motor phase error A motor phase is not connected.
• Check P539
• Check motor connection
16.1 Magnetisation current
monitoring
"Magnetisation current
monitoring"
Required exciting current not achieved at moment of switch-
on.
• Check P539
• Check motor connection
E018 18.0 Reserved
18.1 Reserved
18.2 Reserved