5 Parameter
BU 0155 en-3520 81
P370 PLC status RD
(hex)
(bin)
Display of the actual PLC status.
Value (Bit) Meaning
Parameter P350 was set in the "Activate internal PLC" function
The internal PLC is active.
2 Stop active
The PLC program is in "Stop" status.
3 Debug active
The error checking of the PLC program runs.
The PLC has an error
However, PLC User Errors 23.xx are not displayed.
5 PLC halted
The PLC program has been halted (Single Step or Breakpoint).
6 Scope Memory used
A function block uses the memory area for the oscilloscope
function of the NORDCON software Because of this, the
oscilloscope function cannot be used.
5.2.5 Control terminals
P400 Function Analogue input RD
Other applicable parameter(s) P102, P103, P130, P203, P210, P570
Function Analogue input 1 (= value for P203 from DIP switch S1)
Function Analogue input 2 (= value for P570 from potentiometer P1)
Function Analogue input 3 (= value for P210 from potentiometer P2)
Function Analogue input 4 (= value for P102 / 103 from potentiometer P3)
Display of the function of the relevant DIP switch S1 or potentiometer P1 … P3, if the
DIP switch or the relevant potentiometer is active.
If P130=1 is set, all DIP switches and potentiometers are disabled. "0" = "No function"
is displayed in all arrays.
Value Meaning
The DIP switch or potentiometer is not used.
The DIP switch supplies the value for P203
2 Locking time
The potentiometer supplies the value for P570
3 Starting torque
The potentiometer supplies the value for P210
The potentiometer supplies the value for