NORDAC LINK (SK 155E-FDS / SK 175E-FDS) – Users Manual for Motor Starters as Field Distributors
82 BU 0155 en-3520
P420 Digital inputs RF
Other applicable parameter(s) P130, P428
(= value for digital input DIN1)
(= value for digital input DIN2)
(= value for digital input DIN3)
(= value for PTC input TF)
(= value for Bus In bit 0)
(= value for Bus In bit 3)
(= value for bus digital input BDI1)
[-10] = Bus digital input 2 (= value for bus digital input BDI2)
The factory settings of the arrays [-01] … [-03] depend on the control elements which are used
(configuration of option slots S1 and S2), see Section 2.2.2.2 "Configuration of option slots of the
control level"
Assignment of functions for the various digital inputs.
In order to change parameter values, P130=1 must be set. Otherwise the settings of
P420 can only be read.
Non-permissible settings are ineffective and are not saved.
Value Meaning
The input is not used.
The drive runs with a right-hand direction of
rotation.
(only for array [-01 and -02])
High active
Flank 0 1
1)
2 Enable left
The drive runs with a left-hand direction of
rotation.
(only for array [-01 and -02])
High active
Flank 0 1
1)
The drive runs with a right-hand direction of
rotation.
(only for array [-05 ... -08])
High active
Flank 0 1
1)
The drive runs with a left-hand direction of
rotation.
(only for array [-05 ... -08])
High active
Flank 0 1
1)
5 Disable voltage
Drive runs down to a standstill.
6 Emergency stop
Drive switches to "Switch=on block" after
switching off (termination of selected switch-off
Low active
Acknowledge fault message.
Acknowledgement only possible if the cause of
the message is no longer present.
Flank 0 1
8 PTC input
For evaluating a PTC signal. High active
9 Release the brake
The brake is released manually (signal "high")
or automatically (signal "low")
High active
Automatic mode disabled
2)
Remote control disabled, control only via digital
IOs of the device.
High active
11 Block enable right
Direction of rotation right is blocked. High active
Direction of rotation left is blocked.
PLC program: execution stopped High active
If, depending on parameterP130, Dip switch 2 (S2) or parameter P428 is parameterised to "Automatic
start", no flank is required. A "High Level" is sufficient.
If a digital input is parameterised to this function, the device cannot be enabled with "Enable right" or
"Enable left" in automatic mode. For this the device must first be switched to "Manual mode".